Cảm biến IFL 15-30-10/01YG
Thông số kỹ thuật cảm biến Schmersal IFL 15-30-10/01YG
đại lý schmersal | đại lý IFL 15-30-10/01YG
nhà phân phối schmersal | nhà phân phối IFL 15-30-10/01YG
- 1 Cable entry PG9 x 1.5
- Metal enclosure
- AC 2-wire
- Double-insulated
- Wiring compartment
- Design M30
Ordering data
Product type description |
IFL 15-30-10/01YG |
Article number (order number) |
101056906 |
EAN (European Article Number) |
4030661022413 |
eCl@ss number, version 12.0 |
27-27-40-01 |
eCl@ss number, version 11.0 |
27-27-01-01 |
eCl@ss number, version 9.0 |
27-27-01-01 |
ETIM number, version 7.0 |
EC002714 |
ETIM number, version 6.0 |
EC002714 |
Approvals – Standards
Certificates |
CCC |
General data
Standards |
DIN VDE 0660-208 EN IEC 60947-5-2 |
Housing construction form |
Cylinder, thread |
Installation conditions (mechanical) |
not flush |
Housing material |
Brass |
Housing coating material |
nickel-plated |
Active area |
Plastic |
Material of the nuts |
Brass |
Gross weight |
151 g |
General data – Features
Integral system diagnostics, status |
Yes |
Number of cable wires |
2 |
Mechanical data
Tightening torque of nuts, maximum |
30 Nm |
Mechanical data – Switching distances according EN IEC 60947-5-3
Nominal switching distance Sn |
15 mm |
Mechanical data – Connection technique
Termination |
Screw connection |
Cable section, maximum |
1 x 1.5 mm² |
Mechanical data – Dimensions
ISO thread of the sensor |
M30 |
width across flats |
36 BK |
Length of sensor |
126 mm |
Ambient conditions
Degree of protection |
IP65 |
Ambient temperature |
-25 … +70 °C |
Protection class |
II |
Ambient conditions – Insulation values
Rated impulse withstand voltage Uimp |
4 kV |
Electrical data
Rated supply frequency, minimum |
45 Hz |
Rated supply frequency, maximum |
65 Hz |
Operating current, minimum |
10 mA |
Rated operating voltage |
15 … 250 VAC |
Operating current |
500 mA |
Switching element |
NO contact or NC contact |
Protection circuit integrated |
inductive interference protection |
Switching frequency, approx. |
10 Hz |
VOLT_TYPE_RANGE |
AC |
Electrical data – Digital Output
Voltage drop Ud, maximum |
4.5 V |
Current at Voltage drop Ud |
0.2 A |
Design of control elements |
Two-wire |
Current leakage Ir, maximum |
1 mA |
Status indication
Note (Integral System Diagnostics, status ) |
yellow LED |
Note
Note (General) |
Instead of nuts, a mounting clamp can be provided. Programmable by repositioning the plug-in jumper at the terminal screws |