Rơ le an toàn AES 1185
Thông số kỹ thuật Schmersal AES1185:
| Ordering details
|
|
| Product type description | AES 1185 |
| Article number | 101131903 |
| EAN code | 4030661279435 |
| eCl@ss | 27-37-19-01 |
| Approval
|
|
| Approval | BG USA/CAN |
| Classification
|
|
| Standards | EN ISO 13849-1, IEC 61508 |
| PL | up d |
| Control category | up 3 |
| PFH value | 1.0 x 10-7/h |
| – notice | up to max. 50.000 switching cycles/year and at max. 80% contact load |
| SIL | up 2 |
| Mission time | 20 Years |
| Global Properties
|
|
| Product name | AES 118x |
| Standards | IEC/EN 60204-1, IEC 60947-5-3, EN 954-1, BG-GS-ET-14, BG-GS-ET-20 |
| Compliance with the Directives (Y/N) | Yes |
| Climatic stress | IEC 60947-5-3, BG-GS-ET-14 |
| Mounting | snaps onto standard DIN rail to EN 60715 |
| Terminal designations | IEC/EN 60947-1 |
| Materials | |
| – Material of the housings | Plastic, glass-fibre reinforced thermoplastic |
| – Material of the contacts | Ag-Ni, |
| Weight | 135 g |
| Start conditions | Automatic or Start button |
| Start input (Y/N) | No |
| Feedback circuit (Y/N) | Yes |
| Start-up test (Y/N) | No |
| Reset after disconnection of supply voltage (Y/N) | Yes |
| Automatic reset function (Y/N) | Yes |
| Reset with edge detection (Y/N) | No |
| Pull-in delay | |
| – ON delay with automatic start | adjustable 0,1 / 1.0 s |
| Drop-out delay | |
| – Drop-out delay in case of emergency stop | < 50 ms |
| Mechanical data
|
|
| Connection type | Screw connection |
| Cable section | |
| – Max. Cable section | 2.5 mm² |
| Pre-wired cable | rigid or flexible |
| Tightening torque for the terminals | 0,6 Nm |
| Detachable terminals (Y/N) | No |
| Mechanical life | 50.000.000 operations |
| Electrical lifetime | 100.000 operations for 230 VAC, 6 A (cos φ = 1) |
| restistance to shock | 30 g / 11 ms |
| Resistance to vibration To EN 60068-2-6 | 10…55 Hz, Amplitude 0,35 mm, ± 15 % |
| Ambient conditions
|
|
| Ambient temperature | |
| – Min. environmental temperature | 0°C |
| – Max. environmental temperature | +55 °C |
| Storage and transport temperature | |
| – Min. Storage and transport temperature | −25 °C |
| – Max. Storage and transport temperature | +70 °C |
| Protection class | |
| – Protection class-Enclosure | IP40 |
| – Protection class-Terminals | IP20 |
| – Protection class-Clearance | IP54 |
| Air clearances and creepage distances To IEC/EN 60664-1 | |
| – Rated impulse withstand voltage Uimp | 4.8 kV |
| – Overvoltage category | III To VDE 0110 |
| – Degree of pollution | 2 To VDE 0110 |
| Electromagnetic compatibility (EMC)
|
|
| EMC rating | conforming to EMC Directive |
| Electrical data
|
|
| Rated DC voltage for controls | |
| – Min. rated DC voltage for controls | 20.4 V |
| – Max. rated DC voltage for controls | 27.6 V |
| Rated AC voltage for controls, 50 Hz | |
| – Min. rated AC voltage for controls, 50 Hz | – |
| – Max. rated AC voltage for controls, 50 Hz | – |
| Rated AC voltage for controls, 60 Hz | |
| – Min. rated AC voltage for controls, 60 Hz | – |
| – Max. rated AC voltage for controls, 60 Hz | – |
| Contact resistance | max. 100 mΩ |
| Power consumption | < 5 W |
| Type of actuation | DC |
| Switch frequency | 5 Hz |
| Rated insulation voltage Ui | 250 V |
| Rated operating voltage Ue | 24 VDC ±15% |
| Thermal test current Ithe | 4 A |
| Operating current Ie | 0,2 A |
| Electronic protection (Y/N) | No |
| Inputs
|
|
| Monitored inputs | |
| – Short-circuit recognition (Y/N) | Yes |
| – Wire breakage detection (Y/N) | Yes |
| – Earth connection detection (Y/N) | Yes |
| Number of shutters | 3 piece |
| Number of openers | 3 piece |
| Input resistance | approx. 5000 Ω at GND |
| Input signal “1” | 12 … 30 VDC |
| Input signal “0” | 0 … 2 VDC |
| Cable length | 1000 m with 0,75 mm² (for Rated voltage) |
| Outputs
|
|
| Stop category | 0 |
| Number of safety contacts | 1 piece |
| Number of auxiliary contacts | 0 piece |
| Number of signalling outputs | 0 piece |
| Switching capacity | |
| – Switching capacity of the safety contacts | min.>10 mA, max. 4 A |
| Fuse rating | |
| – Protection of the safety contacts | 4 A gG D-fuse |
| Utilisation category To EN 60947-5-1 | AC-15: 250 V / 2 A DC-13: 24 V / 2 A |
đại lý AES1185, nhà phân phối AES1185, đại lý schmersal AES1185, tài liệu AES1185